Insulation resistance
|
Test voltage
|
125V
|
250V
|
500V
|
1000V
|
Measuring range
(Auto range)
|
4.000/40.00/
200.0MΩ
|
4.000/40.00/400.0/2000MΩ
|
First Effective Measuring range
|
0.1~20MΩ
|
0.1~40MΩ
|
0.1~200MΩ
|
0.1~1000MΩ
|
Mid-scale value
|
5MΩ
|
50MΩ
|
Accuracy
|
|±2%rdg±6dgt
|
Second effective measuring range lower
|
0~0.099MΩ
|
Second effective measuring range upper
|
20.01~
200.0MΩ
|
40.01~
2000MΩ
|
200.1~
2000MΩ
|
1001~
2000MΩ
|
Accuracy
|
|±5%rdg±6dgt
|
Rated current
|
DC 1~1.2mA
|
Output short circuit current
|
1.5mA max
|
Ω/Continuity
|
Auto range
|
40.00/400.0Ω
|
Accuracy
|
|±2%rdg±8dgt
|
Output Voltage on open circuit
|
5V±20%
|
Output short circuit current
|
DC 220±20mA
|
Fuse
|
Quick acting ceramic fuse 0.5A/600V (Ø6.35×32mm)
|
AC Voltage
|
Range
|
AC 20~600V (50/60Hz)
DC -20~-600V/+20~+600V
|
Accuracy
|
|±3%rdg±6dgt
|
General
|
Applicable standards
|
IEC 61010-1 CAT.III 600V, IEC 61557-1,2,4, IEC 61326-1 (EMC), IEC 60529 (IP40)
|
Dimensions / Weight
|
105(L) × 158(W) × 70(D)mm / 600g approx.
|
Power source
|
R6P×6 or LR6×6
|
Accessories
|
7150A (Remote control switch set),
9121 (Shoulder strap), R6P (AA)×6, Instruction Manual
|
Optional
|
7115 (Extension Probe), 8016 (Hook type prod),
8923 (Fuse [0.5A/600V]), 9089 (Carrying Case)
|